1KVA 60/50 400Hz | 2KVA
60/50 400Hz | 3KVA 60/50 400Hz
| Model |
1KSS60400/50400 |
| Capacity |
1KVA/700W |
| Input |
| Voltage |
120V or 220V Input requirement 15A@120V
8.2A@220V |
| Voltage Range |
120V -15%/+20% or 220V -15%/+20% |
| Frequency |
50Hz or 60Hz |
| Phase |
Single |
| Output |
| Voltage |
120V ±20% |
| Voltage Regulation |
±1% |
| Frequency |
400Hz |
| Frequency Regulation |
±0.016Hz (Xtal oscillator) |
| Harmonic Distortion |
<3% at 100% linear load |
| Output Waveform |
Pure Sinewave |
| Output Current @.7pf |
120V-8.3A, 220V-4.6A |
| Non-linear Peak Current |
120V-12.4A, 220V-6.7A for 30 sec. |
| Power Factor |
0.7 |
| Efficiency |
| AC to AC |
>85% |
| Overload Capacity |
110% continuous,110-150% load 30 seconds,
over 150% causes unit to shut down. Auto restart upon removal of the
overload. |
| Short Circuit |
Unit will cut off and must be manually
restarted |
| EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at
70dB |
| Over Temperature |
Inverter auto cut-off when heat sink
temp over 80ºC |
| Audible
Alarm |
| Overload |
Sounds continuously |
| Converter Fault |
Sounds continuously |
| Indicator |
| LCD |
Converter status, Input & Output voltage
- frequency, loading % |
| LED |
| Line(utility power on): Green LED |
Inverter (converter power output): Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Environment |
| OperationTemp. |
-10-50%ºC; 14-122ºF |
| Relative Humidity |
20-90% non-condensing |
| Audible Noise |
Less than 45dB (at 1 meter) |
| Physical |
| Net Weight |
144lbs/64.8kg |
| Width |
7 1/8in/18.1cm |
| Depth |
21 3/8in/54.3cm |
| Height |
19 3/8in/49.3cm |
Back to top
| Model |
2KSS60400/50400 |
| Capacity |
2KVA/1.4kW |
| Input |
| Voltage |
120V or 220V Input Requirement 30A@120V
16.2A@220V |
| Voltage Range |
120V -15%/+20% or 220V -15%/+20% |
| Frequency |
50Hz or 60Hz (400Hz available) |
| Phase |
Single |
| Output |
| Voltage |
120V ±20% |
| Voltage Regulation |
±1% |
| Frequency |
400Hz |
| Frequency Regulation |
±0.016Hz (Xtal oscillator) |
| Harmonic Distortion |
<3% at 100% linear load |
| Output Waveform |
Pure Sinewave |
| Output Current @.7pf |
120V-16.6A, 220V-9A |
| Non-linear Peak Current |
120V-24.6A, 220V-13.5A for 30 sec. |
| Power Factor |
0.7 |
| Efficiency |
| AC to AC |
>85% |
| Overload Capacity |
110% continuous,110-150% load 30 seconds,
over 150% causes unit to shut down. Auto restart upon removal of the
overload. |
| Short Circuit |
Unit will cut off and must be manually
restarted |
| EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at
70dB |
| Over Temperature |
Inverter auto cut-off when heat sink
temp over 80ºC |
| Audible
Alarm |
| Overload |
Sounds continuously |
| Converter Fault |
Sounds continuously |
| Indicator |
| LCD |
Converter status, Input & Output voltage
- frequency, loading % |
| LED |
| Line(utility power on): Green LED |
Inverter (converter power output): Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Environment |
| OperationTemp. |
-10-50%ºC; 14-122ºF |
| Relative Humidity |
20-90% non-condensing |
| Audible Noise |
Less than 45dB (at 1 meter) |
| Physical |
| Net Weight |
144lbs/64.8kg |
| Width |
7 1/8in/18.1cm |
| Depth |
21 3/8in/54.3cm |
| Height |
19 3/8in/49.35cm |
1Specifications subject
to change without notice.
Back to top
| Model |
3KSS60400/50400 |
| Capacity |
3KVA/2.1kW |
| Input |
| Voltage |
120 or 220V Input Requirement 45A@120V
25A@220V |
| Voltage Range |
120V -15%/+20% or 220V -15%/+20% |
| Frequency |
50Hz or 60Hz (400Hz available) |
| Phase |
Single |
| Output |
| Voltage |
120 ±30% |
| Voltage Regulation |
±1% |
| Frequency |
400Hz |
| Frequency Regulation |
±0.016Hz (Xtal oscillator) |
| Harmonic Distortion |
<3% at 100% linear load |
| Output Waveform |
Pure Sinewave |
| Output Current @.7pf |
120V-25A
220V 13.6A |
| Non-linear Peak Current |
120V-37.6A for 30 sec.
220V 20.4A |
| Power Factor |
0.7 |
| Efficiency |
| AC to AC |
>85% |
| Overload Capacity |
110% continuous,110-150% load 30 seconds,
over 150% causes unit to shut down. Auto restart upon removal of the
overload. |
| Short Circuit |
Unit will cut off and must be manually
restarted |
| EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at
70dB |
| Over Temperature |
Inverter auto cut-off when heat sink
temp over 80ºC |
| Audible
Alarm |
| Overload |
Sounds continuously |
| Converter Fault |
Sounds continuously |
| Indicator |
| LCD |
Converter status, Input & Output voltage
- frequency, loading % |
| LED |
| Line(utility power on): Green LED |
Inverter (converter power output): Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Environment |
| OperationTemp. |
-10-50%ºC; 14-122ºF |
| Relative Humidity |
20-90% non-condensing |
| Audible Noise |
Less than 45dB (at 1 meter) |
| Physical |
| Net Weight |
144lbs/64.8kg |
| Width |
7 1/8in/18.1cm |
| Depth |
21 3/8in/54.3cm |
| Height |
19 3/8in/49.35cm |
1Specifications subject to change without notice.
Back to top
|
|